DEGRADED MODE — CACHED ENTITLEMENTS · SENTRIS-DB01 UNREACHABLE · People & Places duty desk
Modify

Opened 13 years ago

Last modified 13 years ago

#36 RESOLVED facilities

Building 8 airlock stuck mid-cycle — two engineers trapped ~15 minutes

Reported by: People & Places Owned by: Site Security — Shoeburyness
Priority: P1 Milestone:
Component: Facilities / Building 8 (Safety) Version:
Keywords: Cc:
Desk: Facilities Legacy ref: DEVCON-1466

Description

The Building 8 personnel airlock stalled mid-cycle with both interlock doors sealed, trapping two engineers for ~15 minutes until Barry on the gate manually vented and released the outer door. No injuries. Reported P1: the airlock must fail safe, and it did not.

Attachments (0)

Change History (2)

comment:1 by Site Security — Shoeburyness, 13 years ago

Both doors latched, cycle hung, two lads sealed in. Barry got them out by hand. Nobody hurt, but not a nice quarter of an hour.

comment:2 by K. Wren, 13 years ago

Watchdog hung on a stuck I/O card. Card swapped, fail-safe vent tested, now defaults OPEN on any hang. But the airlock and the cell-3 interlock share a PLC — raising DEVCON-1471 to split them. Resolved here.